What are the IEC60364-5-52 installation methods A1,A2,B1,B2,C,D,E,F,G?
The IEC 60364-5-52 installation methods are standardized ways to evaluate how electrical cables are installed in a building or structure.
A1
— Insulated conductors in conduit in a thermally insulated wallA2
— Multi-core cable in conduit in a thermally insulated wallB1
— Insulated conductors in conduit on a wooden wallB2
— Multi-core cable in conduit on a wooden wallC
— Single-core or multi-core cable on a wooden wallD
— Multi-core cable in ducts in the groundE
— Multi-core cable in free air (clearance to wall at least 0.3 × cable diameter)F
— Single-core cables, touching in free air (clearance to wall not less than one cable diameter)G
— Single-core cables, spaced in free air (spacing at least one cable diameter)
Refer to IEC 60364-5-52 for the formal definitions and diagrams.