The German workplace regulation ASR A2.2 “Maßnahmen gegen Brände” (measures against fires) specifies in section 5.3 how portable fire extinguishers must be provided in workplaces. Key point: the distance from any location to the nearest fire extinguisher must not exceed 20 m — measured as the actual walking distance, not as the crow flies.
What does “actual walking distance” mean?
Walls, shelves, machines and partitions count: the relevant distance is the path a person would actually have to walk in an emergency to reach the extinguisher — not a straight line through obstacles.
Further requirements of ASR A2.2, section 5.3
Besides the maximum distance, the employer must ensure that:
- fire extinguishers are mounted clearly visible and easily accessible,
- fire extinguishers are preferably placed along escape routes, near exits to the outside, at entrances to stairwells, or at junctions of traffic routes/corridors,
- fire extinguishers are installed protected against damage and weather,
- fire extinguishers are mounted so they can be removed from the bracket without difficulty — a handle height of 0.80 m to 1.20 m has proven practical,
- the locations are marked with the fire safety sign F001 “Fire extinguisher”.
Exception for smaller fire extinguishers
Under normal fire risk, extinguishers with only at least 2 extinguishing units (LE) may be counted towards the basic equipment if access time is reduced — e.g. by halving the maximum distance to the nearest extinguisher (10 m instead of 20 m).
International comparison
ASR A2.2 is a purely German regulation. For comparison, the equivalent rules in the USA and the UK — which, unlike Germany, make the maximum distance depend on the fire class:
| Regulation | Country | Maximum distance |
|---|---|---|
| ASR A2.2, section 5.3 | Germany | 20 m (actual walking distance), independent of fire class |
| OSHA 29 CFR 1910.157(d)(2) | USA | 75 ft ≈ 22.9 m for Class A fires (solid materials) |
| OSHA 29 CFR 1910.157(d)(4) | USA | 50 ft ≈ 15.2 m for Class B fires (flammable liquids/gases) |
| OSHA 29 CFR 1910.157(d)(6) | USA | 75 ft ≈ 22.9 m for Class D fires (combustible metals) |
| NFPA 10 / OSHA eTool | USA | 30 ft ≈ 9.1 m for Class K fires (cooking oils/fats, commercial kitchens) |
| BS 5306-8 | UK | 30 m for Class A, 10 m for Class B and Class F (subtract 5 m for each door that must be opened on the way) |
Assessment: The German requirement of 20 m is within the usual international range. The USA distinguishes by fire class — for Class B the maximum travel distance of 15.2 m is shorter than in Germany. The UK even allows significantly longer distances of 30 m for Class A compared to ASR A2.2, but requires only 10 m for flammable liquids and cooking fats.
Note
ASR A2.2 is a German regulation issued by the Committee for Workplaces (ASTA) and maintained by the Federal Institute for Occupational Safety and Health (BAuA). It specifies the requirements of the German Workplace Ordinance (ArbStättV). Other countries apply different regulatory frameworks.