IEC 60204: Minimum cross sectional area of protective earth bonding wires

IEC 60204-1 specifies when a minimum cross-sectional area applies to protective earth (PE) bonding conductors — and, importantly, when it does not. The requirement depends entirely on how the conductor is installed.

Quick rules

  • If it’s a multicore wire (the PE conductor is part of the same cable as the line conductors): No minimum cross sectional area
  • If it’s a single wire sharing an enclosure with the line conductor (e.g. same conduit/trunking): No minimum cross sectional area
  • If it’s a single wire routed separately from the line conductor:
    • ≥ 2.5 mm² Cu or 16 mm² Al — if protected against mechanical damage (e.g. run in a conduit, trunking, or similar protection)
    • ≥ 4 mm² Cu or 16 mm² Al — if not protected against mechanical damage

Explanation

Per IEC 60204-1 §8.2.1 (EN IEC 60204-1:2018+A1:2025), every protective conductor must satisfy at least one of three conditions: it is part of a multicore cable, it shares a common enclosure with the line conductor, or it meets the minimum cross-sectional areas listed above. This means the minimum size requirement only ever applies to protective conductors run on their own — a PE core inside a multicore cable is acceptable at any size.

Per §8.2.2, a separately installed protective conductor counts as “mechanically protected” when it is installed in a conduit, trunking, or protected in a comparable way — which qualifies it for the lower 2.5 mm² Cu limit.

Additional notes:

  • Steel is permitted as a protective conductor material.
  • Conductive structural parts of the machine or equipment that already satisfy the protection requirements of §6.3.2.2 do not need to be connected to the protective bonding circuit.

Source: EN IEC 60204-1:2018+A1:2025, §8.2.1 and §8.2.2


Check out similar posts by category: Safety Compliance Electronics